是(shi)一(yi)种电(dian)(dian)(dian)压(ya)(ya)(ya)(ya)(ya)变(bian)压(ya)(ya)(ya)(ya)(ya)设备,通常是(shi)指交流电(dian)(dian)(dian)压(ya)(ya)(ya)(ya)(ya)变(bian)换包括升(sheng)压(ya)(ya)(ya)(ya)(ya)和降(jiang)压(ya)(ya)(ya)(ya)(ya)功(gong)能。一(yi)般发电(dian)(dian)(dian)站的(de)电(dian)(dian)(dian)力要(yao)(yao)经过升(sheng)压(ya)(ya)(ya)(ya)(ya)电(dian)(dian)(dian)力变(bian)压(ya)(ya)(ya)(ya)(ya)器(qi)再输送到电(dian)(dian)(dian)网中(zhong),而终端居(ju)民用(yong)(yong)(yong)电(dian)(dian)(dian)需要(yao)(yao)安(an)装降(jiang)压(ya)(ya)(ya)(ya)(ya)电(dian)(dian)(dian)力变(bian)压(ya)(ya)(ya)(ya)(ya)器(qi),负(fu)责把10kV或(huo)20KV高(gao)压(ya)(ya)(ya)(ya)(ya)电(dian)(dian)(dian)降(jiang)压(ya)(ya)(ya)(ya)(ya)到220V和380V市供用(yong)(yong)(yong)户使用(yong)(yong)(yong)。无论是(shi)升(sheng)压(ya)(ya)(ya)(ya)(ya)电(dian)(dian)(dian)力变(bian)压(ya)(ya)(ya)(ya)(ya)器(qi)还是(shi)降(jiang)压(ya)(ya)(ya)(ya)(ya)电(dian)(dian)(dian)力变(bian)压(ya)(ya)(ya)(ya)(ya)器(qi)在运行前都要(yao)(yao)进行安(an)全检(jian)查,以下是(shi)具(ju)体检(jian)查内容(rong)。

一、电力变压(ya)器投入(ru)运(yun)行(xing)前的检查内容(rong)

(1)型号(hao)和(he)规(gui)格(ge)的检查型号(hao)和(he)规(gui)格(ge)是否符合要求

(2)各种保护(hu)装置的检(jian)查熔断器的规格型号是否(fou)符合要求;报警(jing)系(xi)统、继电(dian)(dian)(dian)保护(hu)系(xi)统是否(fou)完好(hao),工作是否(fou)可靠(kao):避雷装置是否(fou)完好(hao);气(qi)(qi)体(ti)继电(dian)(dian)(dian)器是否(fou)完好(hao),内(nei)部(bu)有(you)无(wu)气(qi)(qi)体(ti)存在,如有(you)气(qi)(qi)体(ti)应(ying)打开放气(qi)(qi)阀盖,放掉(diao)气(qi)(qi)体(ti)(图8-36),检(jian)查浮筒、活动挡板和水(shui)银开关动作位置是否(fou)正确气(qi)(qi)油(you)据(ju)被开关底率以下是电(dian)(dian)(dian)力变压器外形图和原理图(tu)。

电力变压器外形图和气体继电器原理图.jpg

(3)监视装置的检查(cha)各(ge)测量仪(yi)表的规格是否(fou)符(fu)合要求,是否(fou)完好;油温指(zhi)示(shi)器、油位显示(shi)器是否(fou)完好,油位是否(fou)在与环(huan)境温度相应的油位线上。

(4)外观检(jian)查箱体(ti)各个部(bu)分有无渗油(you)现象;防爆膜是(shi)否完好;箱体(ti)是(shi)否可(ke)(ke)靠地接地;各电压级的出线套管是(shi)否有裂缝(feng)、损伤,安装是(shi)否牢(lao)(lao)靠;导电排及电缆连接处是(shi)否牢(lao)(lao)固可(ke)(ke)靠。

(5)消防设备的(de)检查数量和(he)种类是否符(fu)合(he)规定要求。

(6)测量(liang)各(ge)电压(ya)级绕组对(dui)地的绝缘电阻(zu)20~30千伏(fu)的变(bian)(bian)压(ya)器不(bu)低于300兆(zhao)欧(ou),3~6千伏(fu)的变(bian)(bian)压(ya)器不(bu)低于200兆(zhao)欧(ou),0.4千伏(fu)以下的变(bian)(bian)压(ya)器不(bu)低于90兆(zhao)欧(ou)。

电力升压变压器.jpg

二(er)、变压器(qi)投入运行中应(ying)进行的检查工作

为保(bao)证变压器(qi)安全运行(xing)(xing),在变压器(qi)投入运行(xing)(xing)中要定期检查,以提高变电质量和及(ji)时(shi)发(fa)现故障及(ji)时(shi)消(xiao)除。

(1)监视仪(yi)表(biao)电(dian)压(ya)表(biao)、电(dian)流表(biao)、功率(lv)表(biao)等应每小(xiao)时(shi)(shi)抄(chao)表(biao)一(yi)次(ci);在(zai)(zai)过载情况(kuang)下运(yun)行(xing)时(shi)(shi),应每半(ban)小(xiao)时(shi)(shi)抄(chao)表(biao)一(yi)次(ci);电(dian)表(biao)不(bu)在(zai)(zai)控制(zhi)室(shi)时(shi)(shi)每班至少抄(chao)表(biao)两次(ci)。温(wen)度(du)计安(an)装在(zai)(zai)配电(dian)盘上(shang)(shang)的录(lu)电(dian)流数(shu)值时(shi)(shi)同时(shi)(shi)记录(lu)温(wen)度(du);温(wen)度(du)计安(an)装在(zai)(zai)变压(ya)器(qi)上(shang)(shang)的应在(zai)(zai)巡视变压(ya)器(qi)时(shi)(shi)进行(xing)记・在(zai)(zai)记

(2)现场(chang)检(jian)(jian)(jian)查(cha)(cha)有值班人员的应每(mei)班检(jian)(jian)(jian)查(cha)(cha)一次(ci),每(mei)天至少(shao)检(jian)(jian)(jian)查(cha)(cha)一次(ci),每(mei)星期进行一次(ci)夜间(jian)检(jian)(jian)(jian)查(cha)(cha)。无固定人员值班的至少(shao)每(mei)两月检(jian)(jian)(jian)查(cha)(cha)一次(ci)。有特殊情(qing)况(kuang)或气候(hou)急剧变化(hua)时要进行及(ji)时检(jian)(jian)(jian)查(cha)(cha),定期检(jian)(jian)(jian)查(cha)(cha)的内容有:

1)检查磁套管表(biao)面(mian)是否(fou)清洁(jie),有无破损(sun)裂纹及放电(dian)痕迹,螺栓(shuan)有无损(sun)坏(huai)及其(qi)他异常情况加发(fa)现上述缺陷,应尽快停(ting)电(dian)检修

2)检查(cha)箱壳有无滲(shen)油和漏油现象(xiang),严(yan)重的要及时处(chu)理。散热管温度是(shi)否均匀。

3)检查贮油柜的(de)油位高度是否正常,若发现油面过低(di)应加油;油色是否正常,必要时进行油样化验

4)检查(cha)油面温(wen)度计的温(wen)度与室(shi)温(wen)之差(cha)(温(wen)升)是(shi)否符合规定,对照负载情况,是(shi)否因变压器内部故(gu)障而引起过热

5)观察防(fang)爆管上(shang)的防(fang)爆膜是(shi)否完好,有无(wu)冒(mao)油现象。

降压变压器检查

6)观察导(dao)电排及电缆(lan)接头处有(you)无发(fa)热(re)变色现象,如贴有(you)示温蜡片的(de),应(ying)检(jian)查蜡片是否熔化,如有(you)此种(zhong)现象,应(ying)停电检(jian)查,找出原因修复

7)注意变压(ya)器有无异常声(sheng)响,或(huo)响声(sheng)是(shi)否较以前增大

8)检查箱体(ti)接地是否良(liang)好。

9)变压器室(shi)内(nei)消(xiao)防设备是否完整良好(hao)。

10)呼吸(xi)器内的干燥剂是(shi)否吸(xi)潮变(bian)色,需要(yao)时进(jin)行烘干处(chu)理(li)或(huo)调换。

11)定期(qi)进(jin)行(xing)油(you)(you)样化(hua)验。取(qu)油(you)(you)样可用图(tu)所示的溢流(liu)法。取(qu)样瓶(ping)成清者(zhe)、干爆不近光,先用软管(guan)与放油(you)(you)阅(yue)门(men)接通(tong),打开门(men),先放掉一部分油(you)(you)、以(yi)冲洗阅(yue)门(men)及软管(guan)的内表(biao)面(mian)然后再(zai)放些油(you)(you)冲洗取(qu)样瓶(ping)和(he)软管(guan)外表(biao)面(mian)。清洗完毕后,将软管(guan)插入取(qu)样瓶(ping)底部,瓶(ping)内盛满油(you)(you)后,使油(you)(you)再(zai)溢出(chu)少许,在溢出(chu)的过程中拉出(chu)软管(guan),盖紧(jin)瓶(ping)盖,送(song)交(jiao)化(hua)验。

以(yi)(yi)是就(jiu)对电(dian)力变压(ya)器运行(xing)前和运行(xing)中的检(jian)查(cha)项目标准。要按每(mei)个步骤逐一检(jian)查(cha)。此外变压(ya)器应安(an)装在(zai)专用变电(dian)室(shi)内,并设有高压(ya)警告标志,外人不得靠(kao)近(jin)和攀爬高压(ya)配电(dian)室(shi)。进出(chu)变压(ya)器室(shi)时,应及(ji)时关门上锁以(yi)(yi)防(fang)小动(dong)物窜入(ru)而引起重(zhong)大事故。


热销产品 了解更多+

配电柜生产厂家为您提供最新,最全,最权威的低压配电柜成套、配电箱、plc控制柜行业信息和恒温恒湿控制柜价格咨询服务,最专业的技术指导,做中国最有影响力的配电设备生产供应商

地(di)址:广东省广州市番禺区(qu)石基镇金龙路44号中润工业园(yuan)

24小(xiao)时服(fu)务热(re)线:13697432957 电子邮箱(xiang):253106211@qq.com

全国销售(shou)区域(yu):广东(dong)深圳、东(dong)莞、佛山、惠州、中(zhong)山、珠海(hai)(hai),广西(xi),安徽,福建,江西(xi),河南,河北,湖北,湖南,海(hai)(hai)南,四川,贵州,云南,陕(shan)西(xi),甘肃,山西(xi),内蒙古,宁夏(xia)

Copyright 2001 - 2015    广州J9九游会AG电控设(she)备有限公司

广州J9九游会AG自动化控(kong)制设备有限(xian)公司

友链: 


扫一扫,免费体(ti)验电(dian)控解决(jue)方案

二维码1 二维码1

在(zai)线客服

二维码1
咨询热线 13697432957